Best OpenControl Modbus Ethernet OPC Server for Automation

Written by

in

How to Configure OpenControl Modbus Ethernet OPC Servers Integrating industrial automation equipment requires robust translation tools. The OpenControl Modbus Ethernet OPC Server bridges the gap between Modbus TCP/IP-compatible hardware and OPC-compliant client applications like SCADA, HMI, or Historian systems. This technical guide outlines the step-by-step process to successfully install, configure, and test your communication links. Prerequisites and System Checklist

Before launching the software, ensure you have gathered the necessary network data and system permissions:

IP Addresses: Dedicate static IP addresses for both the host PC and the target Modbus slave devices.

Modbus Map: Obtain the manufacturer’s documentation detailing the register addresses (coils, discrete inputs, input registers, and holding registers).

Network Port: Verify that TCP Port 502 (the standard Modbus TCP port) is open on your local firewall.

Administrative Rights: Ensure your Windows user account has full administrative privileges to register OPC COM/DCOM components. Step 1: Install and Initialize the Server

Download the OpenControl Modbus Ethernet OPC Server installation package. Right-click the installer and select Run as Administrator.

Follow the on-screen prompts, accept the license agreement, and complete the installation wizard.

Launch the OpenControl configuration utility from your desktop or start menu. Step 2: Create a Communication Channel

The channel defines the physical or virtual network interface used to communicate with your field devices.

In the configuration tree view, right-click the root node and select Add Channel (or click the Channel icon on the toolbar).

Assign a unique name to the channel (e.g., Ethernet_Network_1).

Select Modbus Ethernet or Modbus TCP/IP from the network type dropdown menu.

Configure the network adapter properties. Select the specific Local Network Interface Card (NIC) IP address that binds the server to the industrial network. Step 3: Define Your Modbus Devices

A channel can host multiple devices. You must add each PLC, controller, or sensor explicitly.

Right-click your newly created channel and select Add Device.

Name the device according to your plant naming conventions (e.g., PLC_Chiller_01). Enter the IP Address of the target physical hardware. Specify the Port Number (Default is 502).

Set the Device ID (also known as Unit ID or Slave ID). For direct Modbus TCP communication, this is often set to 1, but it must match your device configuration.

Adjust timing parameters if your network experiences latency:

Timeout: The duration the server waits for a response (Default: 1000ms).

Retries: The number of times the server attempts a failed request before flagging a bad quality tag (Default: 3). Step 4: Configure the OPC Tags

Tags represent the individual data points read from or written to the Modbus registers. Right-click your defined device and select Add Tag. Input a Tag Name (e.g., Temperature_Sensor).

Select the appropriate Data Type matching your PLC configuration (e.g., Short, Word, Float, Boolean).

Enter the Modbus Address using the correct syntax. OpenControl servers generally map addresses using standard prefixes: 0xxxxx: Coils (Read/Write Digital) 1xxxxx: Discrete Inputs (Read-Only Digital) 3xxxxx: Input Registers (Read-Only Analog) 4xxxxx: Holding Registers (Read/Write Analog)

Set the Scan Rate in milliseconds to determine how frequently the server polls this specific data point.

Tip: For large deployments, utilize the bulk import feature to upload your tag dictionary via a CSV spreadsheet to save time. Step 5: Test and Verify the Connection

Never connect your SCADA software until you have verified data integrity locally.

Locate and launch the OPC Quick Client utility included with the OpenControl installation suite.

Connect to the local OPC server registry (usually named something similar to OpenControl.ModbusEthernet.1).

Browse the tag tree to find your configured channel and device.

Check the Value, Quality, and Timestamp columns for your tags.

Good Quality: The server is successfully polling data from the machine.

Bad Quality: Check your physical ethernet connections, IP addressing, and register maps. Step 6: DCOM and Remote Client Connection

If your OPC client resides on a different PC than the OPC server, you must adjust Windows Distributed Component Object Model (DCOM) settings.

Open the Windows Run dialog (Win + R), type dcomcnfg, and press Enter.

Navigate to Component Services > Computers > My Computer > DCOM Config.

Locate your OpenControl OPC Server entry, right-click, and choose Properties.

Under the Security tab, explicitly grant Launch and Activation Permissions and Access Permissions to the relevant user groups or network administrators. To tailor these steps to your system, let me know: The exact model of the hardware device you are connecting

The OPC client software you plan to use (e.g., Ignition, Wonderware, FactoryTalk)

If your architecture requires communication across different subnets

I can then provide specific address formatting templates or exact DCOM setup adjustments.